Recirculating Coolers – Model 4100 Liquid-to-Liquid Cooler
Working Temperature Range: Facility water +10° to 60°C
Maximum Process Temperature: 60°C
Temperature Stability: ±0.4°C
Cooling Capacity: 10,000 watts based on 10°C Δ T
Features
- Protects precision equipment from facility water contaminants
- Quiet, energy-efficient liquid-to-liquid heat removal
- Displays temperature and pressure or flow rate information
- Built-in temperature and low flow alarms
Specification | |
Temperature Range | Facility water +10°C至60°C |
Cooling Capacity (W/BTU) | 15000/52855 based on 15°CΔT¹ 10000/34100 based on 10°CΔT¹ 4500/5345 based on 5°CΔT¹ |
Power Requirements (VAC/Hz) | 200-240/50/60(plug for 230V) |
Standard Pump | Turbine Pump |
Maximum Pressure psi (bar) | 100(6.9) |
Maximum Flow gpm (l/min) | 3.5(13.2) |
Part Number 200-240 VAC / 50-60Hz | 4150T21A330D |